BHS AND REDS INSTALLATION MANUAL
64
D
D ACCEPTANCE TEST PROCEDURE
ACCEPTANCE TEST
The Acceptance Test is a test to be carried out together with the customer in order to certify
that Datalogic reading station fulfils the project specifications. The customer’s acceptance of
the system is reported in the Reader Performance Acceptance Form attached below. This
procedure must be used for all the readers: Scanners, Imagers, Cameras, ………
PREREQUISITES:
A certain number of valid parcels, as agreed with the customer and as defined later on,
with valid bar code labels must be available on site
The conveyor and its system controller must be perfectly working for at least the part
involved in the interaction with Datalogic Automation reading station
There must be the possibility to analyse immediately all the possible no read situations
The customer must supply all the logistic resources for the parcels and code availability
on site and their handling
A customer representative must be present on site for test validation and, in case of
positive results, for Acceptance Test Report signing.
WHAT ACCEPTANCE TEST INCLUDES:
Short pre-test briefing with the customer for Datalogic Automation Acceptance Test
Procedure discussion and acceptance.
Assistance on site during the test.
Result verification.
Filling a short report for a written acceptance of the customer.
The attached Reader Performance Acceptance Form below must be compiled and
signed by the customer representatives.
REQUIRED RESOURCES:
Who: Datalogic Automation subsidiary Technical Support or Datalogic Automation Certified
Technical Personnel.
Timing: the usual amount of Datalogic Automation resources for a standard Acceptance
Test is 3 hours fixed for test preparation plus 3 hours per reading station.
All bar codes used in the test that could not be read, must be immediately recognized by
the parts, analyzed and verified with a code verifier